Page actions
instrument / verified-clean
Moist Air Enthalpy Calculator
The current ledger marks this instrument verified clean within the source-bound verification corpus.
Inspectable records
Ledger state
The current ledger marks this instrument verified clean within the source-bound verification corpus.
- Area
- Thermodynamics, Fluids & Aero
- Tranche
- tranche-4
- Evidence ID
- t4-072
- Ledger rows
- 1
No ledger note is attached.
Review findings
The formula can pass for explicitly supplied T in degrees Celsius and W in kg/kg dry air. The catalog entry is not complete because it also advertises RH as an input without specifying pressure, saturation-pressure calculation, or conversion behavior. The empty honest_label should be replaced with wording such as: approximate moist-air enthalpy per kg dry air; T in degrees Celsius; W in kg/kg dry air; RH input requires pressure and a psychrometric model.
Formula and scope findings
- The formula h=1.006T+W(2501+1.86T) is the standard approximate moist-air enthalpy formula when T is dry-bulb temperature in degrees Celsius and W is humidity ratio in kg water vapor per kg dry air.
- The input declaration says W or RH, but no relative-humidity conversion formula is provided. Converting RH to W requires total pressure and a saturation-vapor-pressure model, so RH alone is insufficient.
Unit assumptions
- T must be in degrees Celsius, not kelvin or degrees Fahrenheit.
- W must be a dimensionless mass ratio in kg water vapor/kg dry air; it must not be entered as percent or directly as g/kg without conversion.
- The output h is in kJ/kg dry air.
- The empirical constants imply the usual psychrometric reference state and approximation; the reference convention should be documented if high accuracy is claimed.
- If RH is accepted, total barometric pressure and the saturation-vapor-pressure correlation must also be specified.
Boundary hardening
Known limit · flagged by the author
An extreme but representable JavaScript input causes the enthalpy multiplication to overflow to Infinity. The calculator should reject or explicitly flag this result rather than treating it as a valid physical enthalpy. A separate unit-convention ambiguity also permits materially different physical interpretations.
Errata and corrections
No applied erratum is attached to this unique-name record.
Inspectable example
4 review vectors are recorded. One source-bound sample is shown below.
{
"inputs": {
"T_C": 25,
"W_kg_per_kg_dry_air": 0.01
},
"expected_outputs": {
"h_kJ_per_kg_dry_air": 50.625
},
"working": "h=1.006(25)+0.010[2501+1.86(25)]\n=25.150+0.010[2501+46.500]\n=25.150+0.010(2547.500)\n=25.150+25.475\n=50.625 kJ/kg dry air"
}Related workflows
Sources and evidence
These pointers bind the page to evidence. They do not grant authority or collapse verification into deployment.
VERIFIED_LEDGER.json · VERIFIED_CLEANevidence-tranche4/tranche4-results.jsonBOUNDARY_HAZARD_CATALOG.json