Source: https://guthlabs.ai/docs/instruments/nec-iec-conduit-fill-calculator/

instrument / verified-clean

# NEC/IEC Conduit Fill Calculator

The current ledger marks this instrument verified clean within the source-bound verification corpus.

Status: **VERIFIED_CLEAN**Lifecycle: **verified-clean**

## Inspectable records

[01**Overview**Purpose and lifecycle](<https://guthlabs.ai/docs/instruments/nec-iec-conduit-fill-calculator/>)[02**Mechanism**Method and assumptions](<https://guthlabs.ai/docs/instruments/nec-iec-conduit-fill-calculator/mechanism/>)[03**Implementation**Binding and validation](<https://guthlabs.ai/docs/instruments/nec-iec-conduit-fill-calculator/implementation/>)[04**Qualification**Evidence and errata](<https://guthlabs.ai/docs/instruments/nec-iec-conduit-fill-calculator/qualification/>)

## Ledger state

The current ledger marks this instrument verified clean within the source-bound verification corpus.

**Area**: Electrical & Electronics Engineering — Circuits, Power Systems, Electronics Lab

**Tranche**: tranche-7

**Evidence ID**: t7-106

**Ledger rows**: 1

No ledger note is attached.

## Review findings

The listed formula is directionally correct only after the NEC fill-percentage rule is completed and the correct table areas are selected. This instrument needs explicit NEC versus IEC logic, code edition and jurisdiction, raceway type, conductor construction and insulation, conductor-category counting rules, and a precise definition of max additional conductors before it can be labeled as more than a reference estimate. Always verify against the current locally adopted electrical code.

### Formula and scope findings

- The stated 40% rule is incomplete and is attributed to the wrong table: under NEC Chapter 9 Table 1, maximum fill is 53% for one conductor, 31% for two conductors, and 40% for three or more conductors. Chapter 9 Table 4 supplies raceway dimensions and Table 5 supplies conductor dimensions.

- The formula must use the conductor's overall insulated outside area, not the bare-metal conductor cross-sectional area. The applicable Chapter 9 Table 5 area depends on conductor size, insulation type, voltage rating, and construction.

- The NEC and IEC methods are not interchangeable. An IEC jurisdiction requires its applicable national or IEC-based raceway dimensions, conductor outside diameters, and fill rules; a simple jurisdiction toggle is insufficient.

- Max additional conductors is ambiguous unless the size, insulation type, and construction of every added conductor are specified. The vectors below assume all added conductors match the listed conductor type.

- Equipment grounding conductors, bonding conductors, neutrals, and cable assemblies have special counting and sizing rules that are not represented by the stated plain arithmetic formula.

### Unit assumptions

- All worked vectors use NEC customary units: conduit and conductor areas are in square inches, and conduit trade sizes are US trade sizes.

- Conductor areas are insulated outside areas from the NEC-style table values, not copper-metal areas.

- Fill percentage is calculated as total insulated conductor area divided by the applicable conduit internal area, multiplied by 100.

- The vectors use EMT conduit and individual copper THHN/THWN-2 conductors, with no cable assemblies, fittings, or special local amendments.

- For max additional conductors, every added conductor is assumed to have the same size and insulation area as the listed conductor.

- The 53%, 31%, and 40% fill limits are treated as NEC Chapter 9 Table 1 limits for one, two, and three-or-more conductors, respectively.

## Boundary hardening

**BREAK_CLAIMED** · SELF_FLAGGED

A zero-area or invalid conduit lookup can cause an undefined division instead of a required rejection, and the grounding-conductor counting convention is not specified, producing different max-additional results.

## Errata and corrections

No applied erratum is attached to this unique-name record.

## Inspectable example

4 review vectors are recorded. One source-bound sample is shown below.

````
{
  "inputs": {
    "jurisdiction": "NEC",
    "conduit_type": "EMT",
    "trade_size": "3/4 in",
    "conductors": [
      {
        "material": "copper",
        "size": "12 AWG",
        "insulation": "THHN/THWN-2",
        "count": 3
      }
    ]
  },
  "expected_outputs": {
    "conduit_internal_area_in2": 0.533,
    "allowed_fill_percent": 40,
    "allowed_area_in2": 0.2132,
    "total_conductor_area_in2": 0.0399,
    "fill_percent": 7.4859,
    "passes": true,
    "max_additional_matching_conductors": 13
  },
  "reference_data": {
    "conduit_row": {
      "trade_size": "3/4 in",
      "internal_area_in2": 0.533,
      "source_convention": "NEC Chapter 9 Table 4, EMT; widely tabulated standard NEC value"
    },
    "conductor_row": {
      "material": "copper",
      "size": "12 AWG",
      "insulation": "THHN/THWN-2",
      "outside_area_in2": 0.0133,
      "source_convention": "NEC Chapter 9 Table 5, insulated copper conductor; widely tabulated standard NEC value"
    },
    "fill_rule": {
      "conductor_count": "3 or more",
      "allowed_fill_percent": 40,
      "source_convention": "NEC Chapter 9 Table 1; widely tabulated standard NEC value"
    }
  },
  "working": "1. Conduit internal area = 0.533 in².\\n2. Three conductors use the 40% limit. Allowed area = 0.40 × 0.533 = 0.2132 in².\\n3. Existing conductor area = 3 × 0.0133 = 0.0399 in².\\n4. Fill = (0.0399 ÷ 0.533) × 100 = 7.4859%.\\n5. Remaining allowed area = 0.2132 − 0.0399 = 0.1733 in².\\n6. Additional conductors = floor(0.1733 ÷ 0.0133) = floor(13.0301) = 13.\\n7. Check: 16 × 0.0133 = 0.2128 in² ≤ 0.2132 in²; 17 × 0.0133 = 0.2261 in² > 0.2132 in²."
}
````

## Related workflows

No source-defined multi-instrument workflow membership is recorded.

## Sources and evidence

These pointers bind the page to evidence. They do not grant authority or collapse verification into deployment.

- `VERIFIED_LEDGER.json · VERIFIED_CLEAN`

- `evidence-tranche7/tranche7-results.json`

- `BOUNDARY_HAZARD_CATALOG.json`
