# Wire Ampacity Calculator

The current ledger marks this instrument verified clean within the source-bound verification corpus.

Status: **VERIFIED_CLEAN**Lifecycle: **verified-clean**

## Inspectable records

[01**Overview**Purpose and lifecycle](<https://guthlabs.ai/docs/instruments/wire-ampacity-calculator/>)[02**Mechanism**Method and assumptions](<https://guthlabs.ai/docs/instruments/wire-ampacity-calculator/mechanism/>)[03**Implementation**Binding and validation](<https://guthlabs.ai/docs/instruments/wire-ampacity-calculator/implementation/>)[04**Qualification**Evidence and errata](<https://guthlabs.ai/docs/instruments/wire-ampacity-calculator/qualification/>)

## Ledger state

The current ledger marks this instrument verified clean within the source-bound verification corpus.

**Area**: Electrical & Electronics Engineering — Circuits, Power Systems, Electronics Lab

**Tranche**: tranche-7

**Evidence ID**: t7-068

**Ledger rows**: 1

No ledger note is attached.

## Review findings

The supplied honest label is appropriate but incomplete. Before implementation, require material, code edition and jurisdiction, current-carrying-conductor count, terminal temperature rating, conductor installation method, and an explicit distinction between NEC and IEC calculation engines. No interpolation is used in these vectors; every lookup lands exactly on a cited table row or factor.

### Formula and scope findings

- NEC Table 310.16 is not sufficient by itself: its ampacities assume no more than three current-carrying conductors in a raceway or cable, 30 °C ambient, and the applicable conductor material and insulation temperature column.

- The input schema omits conductor material. AWG/kcmil ampacity differs substantially between copper and aluminum, so the material must be an explicit input or a documented default.

- Conductor count is not necessarily current-carrying conductor count. Equipment grounding conductors, some neutrals, and certain control or balanced-circuit conductors may be excluded under NEC rules; the calculator must either request current-carrying conductor count or clearly state its counting convention.

- Ambient-temperature correction and conductor-count adjustment are multiplicative factors, but the result must also be limited by conductor terminal temperature ratings and other applicable code limits.

- Conduit fill is generally a separate physical-fill calculation, not an ampacity derating factor. It may affect how many conductors can be installed and therefore the current-carrying-conductor count, but it should not be applied as an independent ampacity multiplier.

- The formula must specify the insulation rating used for adjustment, normally the 90 °C column for THHN/THWN-2 adjustment, while final allowable ampacity is limited by the applicable 60 °C or 75 °C terminal rating.

### Unit assumptions

- All currents are in amperes, conductor sizes are AWG, and ambient temperature inputs are degrees Celsius.

- The test vectors assume copper conductors, because material is absent from the supplied input schema.

- THHN is treated as having a 90 °C insulation rating for adjustment calculations; final ampacity is limited to the 75 °C terminal column.

- The NEC convention used is NEC 2020: Table 310.16 values at 30 °C ambient and no more than three current-carrying conductors; ambient correction factors from Table 310.15(B)(1); conductor-count adjustment factors from Table 310.15(B)(3)(a); and small-conductor limits from 240.4(D).

- The reported code_max_allowable_ampacity_A is min(adjusted 90 °C ampacity, terminal-temperature ampacity, any applicable small-conductor limit).

## Boundary hardening

**BREAK_CLAIMED** · SELF_FLAGGED

An ambient temperature such as 200 C lies outside the NEC correction-factor table and has no defined derating result. The calculator must reject it; extrapolating a factor or returning a numeric ampacity would be a hazard. The convention probe also shows that the conductor-count field needs an explicit current-carrying-versus-total definition.

## Errata and corrections

No applied erratum is attached to this unique-name record.

## Inspectable example

4 review vectors are recorded. One source-bound sample is shown below.

````
{
  "inputs": {
    "material": "copper",
    "size": "12 AWG",
    "insulation": "THHN",
    "ambient_C": 30,
    "current_carrying_conductors": 3,
    "terminal_rating_C": 75
  },
  "expected_outputs": {
    "base_ampacity_90C_A": 30,
    "adjusted_ampacity_90C_A": 30,
    "terminal_limited_ampacity_A": 25,
    "code_max_allowable_ampacity_A": 20
  },
  "reference_data": {
    "table_310_16_copper_12_AWG": {
      "60C_A": 20,
      "75C_A": 25,
      "90C_A": 30,
      "source_convention": "NEC 2020 Table 310.16"
    },
    "ambient_correction_90C_at_30C": {
      "factor": 1,
      "source_convention": "NEC 2020 Table 310.15(B)(1)"
    },
    "current_carrying_adjustment_for_3": {
      "factor": 1,
      "source_convention": "NEC 2020 Table 310.15(B)(3)(a)"
    },
    "small_conductor_limit_12_AWG": {
      "maximum_A": 20,
      "source_convention": "NEC 2020 240.4(D)"
    }
  },
  "working": "Base 90 °C ampacity = 30 A. Ambient factor at 30 °C = 1.00. Three current-carrying conductors require no adjustment, factor = 1.00. Adjusted ampacity = 30 × 1.00 × 1.00 = 30 A. The 75 °C terminal limit is 25 A, so terminal-limited ampacity = min(30, 25) = 25 A. NEC 240.4(D) limits 12 AWG copper to 20 A, so final code maximum = min(25, 20) = 20 A."
}
````