Composite Wall R-value / U-value Calculator mechanism
The inspectable method record for Composite Wall R-value / U-value Calculator, kept separate from implementation and qualification.
Model scope
The mathematical model is standard under the stated unit assumptions, but the specification needs an explicit input contract for conductivity-based layers versus direct insulation R-values, a q sign convention, and validation rules. The honest label should also state steady-state one-dimensional conduction, no thermal bridging, and whether contact resistances, moisture effects, thermal radiation within cavities, and temperature-dependent material properties are excluded.
- The formulas Rtotal=Σ(L/k)+Rfilms and U=1/Rtotal are standard for steady-state, one-dimensional conduction when all quantities use compatible units.
- The data specification mentions both material thermal conductivity k and insulation R-values, but does not define whether a layer may be entered as an R-value. If an insulation R-value is used, it must be added directly and must not also be calculated from L/k or double-counted.
- q=U·A·ΔT correctly gives signed heat-transfer rate in watts, but the required sign convention and whether the displayed result is signed heat flow or absolute heat loss/gain are unspecified.
- The specification does not state whether Rfilms means exactly one interior and one exterior surface resistance, nor whether contact resistances are excluded.
Units and conventions
- For SI calculations, layer thickness L is in metres, thermal conductivity k is in W/(m·K), film resistances and total R-value are in m²·K/W, U is in W/(m²·K), area A is in m², ΔT is in K or °C difference, and q is in W.
- A temperature difference of 1 K equals a temperature difference of 1 °C; absolute Celsius temperatures must not be substituted for ΔT.
- Thickness values supplied in millimetres must be converted to metres before dividing by k when k is in W/(m·K).
- Rfilms are assumed to be additive surface resistances in m²·K/W.
Inspectable vector
One of 4 source-bound review vectors:
{
"inputs": {
"layers": [
{
"material": "brick",
"thickness": 0.1,
"thickness_unit": "m",
"k": 0.5,
"k_unit": "W/(m·K)"
},
{
"material": "mineral wool insulation",
"thickness": 0.1,
"thickness_unit": "m",
"k": 0.04,
"k_unit": "W/(m·K)"
},
{
"material": "gypsum board",
"thickness": 0.012,
"thickness_unit": "m",
"k": 0.12,
"k_unit": "W/(m·K)"
}
],
"film_resistances": {
"inside": 0.13,
"outside": 0.04,
"unit": "m²·K/W"
},
"area": 40,
"area_unit": "m²",
"delta_T": 25,
"delta_T_unit": "K"
},
"expected_outputs": {
"Rtotal": 2.97,
"Rtotal_unit": "m²·K/W",
"U": 0.3367003367,
"U_unit": "W/(m²·K)",
"q": 336.7003367,
"q_unit": "W"
},
"working": "Brick: L/k = 0.1/0.5 = 0.2 m²·K/W. Insulation: 0.1/0.04 = 2.5 m²·K/W. Gypsum: 0.012/0.12 = 0.1 m²·K/W. Films: 0.13 + 0.04 = 0.17 m²·K/W. Rtotal = 0.2 + 2.5 + 0.1 + 0.17 = 2.97 m²·K/W. U = 1/2.97 = 0.3367003367 W/(m²·K). q = U·A·ΔT = 0.3367003367·40·25 = 0.3367003367·1000 = 336.7003367 W."
}Failure boundary
BREAK_CLAIMED · SELF_FLAGGED
A zero thermal-conductivity input causes division by zero in L/k, producing undefined R-value, U-value, and heat flow. The instrument must reject k=0 rather than propagate a numeric result.