Diode Bridge Rectifier Loss Estimator mechanism
The inspectable method record for Diode Bridge Rectifier Loss Estimator, kept separate from implementation and qualification.
Model scope
NEEDS_REVIEW because the declared full/half bridge input is not matched by a defined formula, and the units and meaning of load current are not explicit. The honest_label field is empty; the instrument should explicitly label the result as an estimated forward-conduction loss, not total rectifier heat dissipation.
- Ploss=2×Vf×Iload is correct for a conventional full-wave bridge when exactly two diodes conduct and Vf is treated as a constant forward drop.
- The specification accepts bridge type full/half, but provides no formula or unambiguous definition for half. A half-wave rectifier typically uses Ploss=Vf×Iload during conduction; a center-tapped full-wave rectifier also has one conducting diode at a time, so the term half is ambiguous.
- The formula requires Iload to represent the relevant average diode/load current for average conduction loss. If the input is RMS current, peak current, or a time-varying waveform, the formula is insufficient without waveform and diode-model assumptions.
- The output description heat dissipation to plan for could be misleading because the calculated value is only diode forward-conduction loss, not total rectifier thermal design power including switching/reverse-recovery losses, leakage, wiring, or other component losses.
Units and conventions
- Vf must be entered in volts (V).
- Iload must be entered in amperes (A).
- For the stated formula, Iload is assumed to be the average load current during normal full-bridge operation, with two diodes carrying that current.
- Vf is assumed constant and identical for both conducting diodes; diode dynamic resistance and temperature dependence are ignored.
- The output Ploss is in watts (W), since V×A=W.
- The test vectors use bridge_type=full because the supplied formula does not define an unambiguous half-bridge calculation.
Inspectable vector
One of 4 source-bound review vectors:
{
"inputs": {
"diode_Vf": 0.7,
"Vf_unit": "V",
"load_current": 2,
"current_unit": "A",
"bridge_type": "full"
},
"expected_outputs": {
"power_loss_W": 2.8
},
"working": "Two diodes conduct: Ploss=2×Vf×Iload=2×0.7 V×2.0 A=1.4 V×2.0 A=2.8 W."
}Failure boundary
BREAK_CLAIMED · SELF_FLAGGED
The estimator has no stated overflow handling for extreme numeric inputs, and the half-bridge branch is accepted as an input but lacks an explicit formula. Negative-current handling is also undefined and can produce a physically invalid negative loss.