NEC/IEC Conduit Fill Calculator implementation
A source-bound implementation contract for NEC/IEC Conduit Fill Calculator; deployment and executable qualification remain separate.
Binding contract
This record describes what an executable surface must bind and validate. It does not claim that a public calculator, package, or production route is deployed.
- Record owner
- Guth Instruments
- Lifecycle
- verified-clean
- Evidence ID
- t7-106
- Effect
- Computation or source lookup only
Input and validation requirements
A zero-area or invalid conduit lookup can cause an undefined division instead of a required rejection, and the grounding-conductor counting convention is not specified, producing different max-additional results.
Required corrections
No binding erratum is attached to this unique-name record. Implementers must still preserve the declared units, domain, and failure behavior.
Inspectable interface fixture
The sample below is evidence for interface and validation tests, not a production implementation.
{
"inputs": {
"jurisdiction": "NEC",
"conduit_type": "EMT",
"trade_size": "3/4 in",
"conductors": [
{
"material": "copper",
"size": "12 AWG",
"insulation": "THHN/THWN-2",
"count": 3
}
]
},
"expected_outputs": {
"conduit_internal_area_in2": 0.533,
"allowed_fill_percent": 40,
"allowed_area_in2": 0.2132,
"total_conductor_area_in2": 0.0399,
"fill_percent": 7.4859,
"passes": true,
"max_additional_matching_conductors": 13
},
"reference_data": {
"conduit_row": {
"trade_size": "3/4 in",
"internal_area_in2": 0.533,
"source_convention": "NEC Chapter 9 Table 4, EMT; widely tabulated standard NEC value"
},
"conductor_row": {
"material": "copper",
"size": "12 AWG",
"insulation": "THHN/THWN-2",
"outside_area_in2": 0.0133,
"source_convention": "NEC Chapter 9 Table 5, insulated copper conductor; widely tabulated standard NEC value"
},
"fill_rule": {
"conductor_count": "3 or more",
"allowed_fill_percent": 40,
"source_convention": "NEC Chapter 9 Table 1; widely tabulated standard NEC value"
}
},
"working": "1. Conduit internal area = 0.533 in².\\n2. Three conductors use the 40% limit. Allowed area = 0.40 × 0.533 = 0.2132 in².\\n3. Existing conductor area = 3 × 0.0133 = 0.0399 in².\\n4. Fill = (0.0399 ÷ 0.533) × 100 = 7.4859%.\\n5. Remaining allowed area = 0.2132 − 0.0399 = 0.1733 in².\\n6. Additional conductors = floor(0.1733 ÷ 0.0133) = floor(13.0301) = 13.\\n7. Check: 16 × 0.0133 = 0.2128 in² ≤ 0.2132 in²; 17 × 0.0133 = 0.2261 in² > 0.2132 in²."