Voltage Drop Calculator (wire run) implementation
A source-bound implementation contract for Voltage Drop Calculator (wire run); deployment and executable qualification remain separate.
Binding contract
This record describes what an executable surface must bind and validate. It does not claim that a public calculator, package, or production route is deployed.
- Record owner
- Guth Instruments
- Lifecycle
- verified-clean
- Evidence ID
- t7-076
- Effect
- Computation or source lookup only
Input and validation requirements
A zero source voltage produces a finite voltage-drop result but makes the required percentage and guideline pass/fail result undefined. The instrument also has a material one-way-versus-loop-length ambiguity unless the length convention is explicitly captured.
Required corrections
No binding erratum is attached to this unique-name record. Implementers must still preserve the declared units, domain, and failure behavior.
Inspectable interface fixture
The sample below is evidence for interface and validation tests, not a production implementation.
{
"inputs": {
"length": 100,
"length_unit": "ft",
"current": 15,
"current_unit": "A",
"conductor": "copper",
"gauge": "12 AWG",
"area_mm2": 3.31,
"resistivity_ohm_m": 1.68e-8,
"phase_config": "DC",
"source_voltage": 120,
"source_voltage_unit": "V"
},
"expected_outputs": {
"voltage_drop_V": 4.6411,
"voltage_drop_percent": 3.8676,
"pass_3_percent": false,
"pass_5_percent": true
},
"reference_data": {
"copper_resistivity_ohm_m_20C": 1.68e-8,
"copper_resistivity_source_convention": "widely tabulated standard value; CRC/NIST textbook value at approximately 20 °C",
"awg_12_copper_area_mm2": 3.31,
"awg_area_source_convention": "widely tabulated standard AWG cross-sectional-area value",
"feet_to_metres": 0.3048,
"feet_to_metres_source_convention": "exact SI/international definition"
},
"working": "R_per_m = rho / area = 1.68e-8 ohm·m / (3.31e-6 m²) = 0.00507553 ohm/m. R_per_ft = 0.00507553 × 0.3048 = 0.00154702 ohm/ft. DC voltage drop = 2 × L × I × R_per_ft = 2 × 100 ft × 15 A × 0.00154702 ohm/ft = 4.64106 V, rounded to 4.6411 V. Drop percentage = 4.64106 / 120 × 100 = 3.86755%, rounded to 3.8676%. Since 3.8676% > 3%, the 3% check fails; since 3.8676% ≤ 5%, the 5% check passes."