Wire Ampacity Calculator implementation
A source-bound implementation contract for Wire Ampacity Calculator; deployment and executable qualification remain separate.
Binding contract
This record describes what an executable surface must bind and validate. It does not claim that a public calculator, package, or production route is deployed.
- Record owner
- Guth Instruments
- Lifecycle
- verified-clean
- Evidence ID
- t7-068
- Effect
- Computation or source lookup only
Input and validation requirements
An ambient temperature such as 200 C lies outside the NEC correction-factor table and has no defined derating result. The calculator must reject it; extrapolating a factor or returning a numeric ampacity would be a hazard. The convention probe also shows that the conductor-count field needs an explicit current-carrying-versus-total definition.
Required corrections
No binding erratum is attached to this unique-name record. Implementers must still preserve the declared units, domain, and failure behavior.
Inspectable interface fixture
The sample below is evidence for interface and validation tests, not a production implementation.
{
"inputs": {
"material": "copper",
"size": "12 AWG",
"insulation": "THHN",
"ambient_C": 30,
"current_carrying_conductors": 3,
"terminal_rating_C": 75
},
"expected_outputs": {
"base_ampacity_90C_A": 30,
"adjusted_ampacity_90C_A": 30,
"terminal_limited_ampacity_A": 25,
"code_max_allowable_ampacity_A": 20
},
"reference_data": {
"table_310_16_copper_12_AWG": {
"60C_A": 20,
"75C_A": 25,
"90C_A": 30,
"source_convention": "NEC 2020 Table 310.16"
},
"ambient_correction_90C_at_30C": {
"factor": 1,
"source_convention": "NEC 2020 Table 310.15(B)(1)"
},
"current_carrying_adjustment_for_3": {
"factor": 1,
"source_convention": "NEC 2020 Table 310.15(B)(3)(a)"
},
"small_conductor_limit_12_AWG": {
"maximum_A": 20,
"source_convention": "NEC 2020 240.4(D)"
}
},
"working": "Base 90 °C ampacity = 30 A. Ambient factor at 30 °C = 1.00. Three current-carrying conductors require no adjustment, factor = 1.00. Adjusted ampacity = 30 × 1.00 × 1.00 = 30 A. The 75 °C terminal limit is 25 A, so terminal-limited ampacity = min(30, 25) = 25 A. NEC 240.4(D) limits 12 AWG copper to 20 A, so final code maximum = min(25, 20) = 20 A."
}Other records
Sources and evidence
These pointers bind the page to evidence. They do not grant authority or collapse verification into deployment.
VERIFIED_LEDGER.jsonevidence-tranche7/tranche7-results.json