Footing Size Calculator (Preliminary)
The current ledger marks this instrument verified clean within the source-bound verification corpus.
Inspectable records
Ledger state
The current ledger marks this instrument verified clean within the source-bound verification corpus.
- Area
- Mechanical, Civil & Structural Engineering — Statics/Dynamics, Strength of Materials, Machine Design, Civil, HVAC, Vibration
- Tranche
- tranche-5
- Evidence ID
- t5-131
- Ledger rows
- 1
No ledger note is attached.
Review findings
The algebra is correct for preliminary sizing under a centered axial load, positive allowable pressure, compatible units, and a square footing assumption. Verdict is NEEDS_REVIEW because the specification leaves the load basis, gross-versus-net pressure convention, unit contract, and applicability constraints ambiguous. The existing honest label is appropriate but should explicitly state that self-weight, eccentricity/moments, settlement, shear, stability, code minimums, and constructible rounding are excluded.
Formula and scope findings
- A_req=P/qallow is the standard preliminary formula only for a concentric axial load and a uniformly distributed allowable bearing pressure; the specification does not state those constraints.
- The formula does not account for footing self-weight, overburden, eccentricity, moment, shear, settlement, sliding, overturning, or code-required minimum dimensions and rounding.
- The square-footing dimension formula is valid only when a square plan shape is explicitly selected; rectangular footing dimensions are not determined by the provided formulas.
Unit assumptions
- P and qallow must use compatible force units, with qallow expressed as force per unit area.
- Examples using kN and kPa rely on 1 kPa=1 kN/m², so P/qallow produces m².
- Examples using N and kPa require converting qallow from kPa to N/m² before division.
- The calculation assumes P is the load basis appropriate for comparison with the stated allowable soil pressure, but the specification does not identify whether P is service, factored, net, or gross load.
Boundary hardening
BREAK_CLAIMED · SELF_FLAGGED
The plain formula has no stated input validation or load-sign convention. Zero or negative allowable pressure can cause division-by-zero or invalid negative areas, zero load produces a nonphysical zero footing, and a signed compressive load can produce an undefined square root.
Errata and corrections
No applied erratum is attached to this unique-name record.
Inspectable example
4 review vectors are recorded. One source-bound sample is shown below.
{
"inputs": {
"P": 600,
"P_unit": "kN",
"qallow": 200,
"qallow_unit": "kPa",
"shape": "square"
},
"expected_outputs": {
"required_area": 3,
"required_area_unit": "m²",
"square_side": 1.73205,
"square_side_unit": "m"
},
"working": "1. Since 1 kPa=1 kN/m², qallow=200 kN/m². 2. A_req=P/qallow=600 kN ÷ 200 kN/m²=3 m². 3. Square side=√A_req=√3 m=1.73205 m."
}Related workflows
No source-defined multi-instrument workflow membership is recorded.
Sources and evidence
These pointers bind the page to evidence. They do not grant authority or collapse verification into deployment.
VERIFIED_LEDGER.json · VERIFIED_CLEANevidence-tranche5/tranche5-results.jsonBOUNDARY_HAZARD_CATALOG.json