Fuse/Breaker Trip Time Curve Viewer
The current ledger marks this instrument verified clean within the source-bound verification corpus.
Inspectable records
Ledger state
The current ledger marks this instrument verified clean within the source-bound verification corpus.
- Area
- Electrical & Electronics Engineering — Circuits, Power Systems, Electronics Lab
- Tranche
- tranche-7
- Evidence ID
- t7-130
- Ledger rows
- 1
No ledger note is attached.
Review findings
The honest-label text is appropriate but not sufficient to make the computation uniquely defined. NEEDS_REVIEW is required because the spec names IEC 60898 B/C/D and generic fuse families without supplying a normative table or an exact mathematical model. The four vectors use explicitly marked illustrative parameters solely to make arithmetic testable; they must not be presented as manufacturer, IEC, UL, or fuse-standard trip times.
Formula and scope findings
- The specification does not provide numerical curve parameters, breakpoint tables, tolerances, or a defined equation, so an estimated trip time cannot be uniquely computed.
- IEC 60898 B/C/D classifications define characteristic instantaneous-trip current bands, not one exact trip time at each overcurrent multiple. A B/C/D label alone is insufficient for a time-current plot.
- An I²t model normally gives t = K/I², or t = K/M² when expressed using current multiple M. The alternative inverse-time form t = K/(M² - 1) is not universally standard and requires an explicit, instrument-specific definition and fitted K values.
- Breaker thermal-magnetic curves and fuse pre-arcing/clearing curves are different phenomena; one generic formula cannot honestly represent both without separate curve models and definitions.
- The specification does not distinguish fuse pre-arcing time from total clearing time, nor breaker trip mechanism time from total interruption time.
Unit assumptions
- Rated current and fault current are in amperes; fault-current multiple M is dimensionless and equals fault current divided by rated current.
- Estimated trip time is in seconds.
- For the illustrative vectors below, the explicitly supplied generic model is t = K/(M² - 1), with K in seconds and M > 1.
- Rated current must be greater than zero; fault current is computed as rated current multiplied by M.
- The IEC 60898 B/C/D values are characteristic-band boundaries, not exact trip-time guarantees.
Boundary hardening
BREAK_CLAIMED · SELF_FLAGGED
The generic viewer specification has undefined behavior at M = 1, requires explicit handling at the zero-overcurrent boundary, switches between inverse-time and instantaneous branches, and can produce a different validity result if signed current is interpreted literally instead of by magnitude.
Errata and corrections
No applied erratum is attached to this unique-name record.
Inspectable example
4 review vectors are recorded. One source-bound sample is shown below.
{
"inputs": {
"rated_current_A": 20,
"curve_type": "B",
"fault_current_multiple": 3
},
"expected_outputs": {
"fault_current_A": 60,
"estimated_trip_time_s": 0.15,
"curve_point": {
"x_multiple": 3,
"y_time_s": 0.15
}
},
"reference_data": {
"iec_60898_1_curve_band": {
"class": "B",
"instantaneous_trip_band_multiple": "3 to 5 x In",
"lower_boundary_multiple": 3,
"upper_boundary_multiple": 5,
"source_convention": "IEC 60898-1 characteristic band"
},
"generic_model_parameter": {
"curve_type": "B",
"K_s": 1.2,
"source_convention": "illustrative generic parameter supplied for verification; not a normative IEC value"
},
"model": "t_s = K_s/(M^2 - 1)"
},
"working": "M = 3, so fault current = 20 A × 3 = 60 A. M² - 1 = 3² - 1 = 9 - 1 = 8. t = 1.2 s / 8 = 0.15 s. M = 3 is exactly the widely memorized IEC 60898-1 B-curve lower instantaneous-band boundary; that boundary does not itself guarantee a 0.15 s trip time."
}Related workflows
No source-defined multi-instrument workflow membership is recorded.
Sources and evidence
These pointers bind the page to evidence. They do not grant authority or collapse verification into deployment.
VERIFIED_LEDGER.json · VERIFIED_CLEANevidence-tranche7/tranche7-results.jsonBOUNDARY_HAZARD_CATALOG.json