HVAC Heating/Cooling Load Estimator (Envelope Method) implementation
A source-bound implementation contract for HVAC Heating/Cooling Load Estimator (Envelope Method); deployment and executable qualification remain separate.
Binding contract
This record describes what an executable surface must bind and validate. It does not claim that a public calculator, package, or production route is deployed.
- Record owner
- Guth Instruments
- Lifecycle
- verified-clean
- Evidence ID
- t7-127
- Effect
- Computation or source lookup only
Input and validation requirements
The extreme infiltration input produces a mathematical result of 1.08e310 Btu/h, which overflows ordinary IEEE-754 floating-point arithmetic to a non-finite value. The convention probe also exposes a sign ambiguity: reversing the definition of ΔT changes the reported result from +8960 to -8960 Btu/h even though the physical condition is heating.
Required corrections
No binding erratum is attached to this unique-name record. Implementers must still preserve the declared units, domain, and failure behavior.
Inspectable interface fixture
The sample below is evidence for interface and validation tests, not a production implementation.
{
"inputs": {
"system": "US heating",
"surfaces": [
{
"name": "wall",
"area_ft2": 800,
"U_Btu_h_ft2_F": 0.07692307692307693
},
{
"name": "window",
"area_ft2": 100,
"U_Btu_h_ft2_F": 0.5
},
{
"name": "roof",
"area_ft2": 800,
"U_Btu_h_ft2_F": 0.05263157894736842
}
],
"indoor_temperature_F": 70,
"outdoor_temperature_F": 20,
"infiltration_CFM": 100
},
"expected_outputs": {
"temperature_difference_F": 50,
"conduction_Btu_h": 7682.186234818,
"infiltration_Btu_h": 5400,
"total_heating_load_Btu_h": 13082.186234818,
"total_cooling_load_Btu_h": 0
},
"reference_data": {
"wall_nominal_R_value_h_ft2_F_per_Btu": 13,
"wall_U_Btu_h_ft2_F": "1/13 = 0.07692307692307693",
"wall_source_convention": "Widely tabulated standard nominal insulation value, R-13",
"roof_nominal_R_value_h_ft2_F_per_Btu": 19,
"roof_U_Btu_h_ft2_F": "1/19 = 0.05263157894736842",
"roof_source_convention": "Widely tabulated standard nominal insulation value, R-19",
"window_U_Btu_h_ft2_F": 0.5,
"window_source_convention": "Widely tabulated standard value for a representative modern double-glazed window",
"US_infiltration_factor_Btu_h_per_CFM_F": 1.08,
"infiltration_factor_source_convention": "Widely tabulated HVAC standard-air conversion value"
},
"working": "ΔT = 70 − 20 = 50°F. Wall = (1/13)·800·50 = 3076.923076923 Btu/h. Window = 0.50·100·50 = 2500 Btu/h. Roof = (1/19)·800·50 = 2105.263157895 Btu/h. Conduction = 3076.923076923 + 2500 + 2105.263157895 = 7682.186234818 Btu/h. Infiltration = 1.08·100·50 = 5400 Btu/h. Total heating = 7682.186234818 + 5400 = 13082.186234818 Btu/h. Since outdoor temperature is lower, cooling load = 0."
}Other records