HVAC Sensible/Latent Load Calculator implementation
A source-bound implementation contract for HVAC Sensible/Latent Load Calculator; deployment and executable qualification remain separate.
Binding contract
This record describes what an executable surface must bind and validate. It does not claim that a public calculator, package, or production route is deployed.
- Record owner
- Guth Instruments
- Lifecycle
- verified-clean
- Evidence ID
- t4-084
- Effect
- Computation or source lookup only
Input and validation requirements
The calculator has an unavoidable undefined-result trap when total load is zero: SHR becomes 0/0 or a nonzero value divided by zero. The specification also leaves the CFM-versus-mass-flow branch selection, humidity-ratio units, and load sign convention insufficiently defined, allowing materially different outputs or sign reversals.
Required corrections
No binding erratum is attached to this unique-name record. Implementers must still preserve the declared units, domain, and failure behavior.
Inspectable interface fixture
The sample below is evidence for interface and validation tests, not a production implementation.
{
"inputs": {
"system": "metric",
"mass_flow_kg_per_s": 0.5,
"entering_temperature_C": 30,
"leaving_temperature_C": 20,
"entering_humidity_ratio_kg_per_kg_dry_air": 0.018,
"leaving_humidity_ratio_kg_per_kg_dry_air": 0.01,
"hfg_kJ_per_kg": 2500
},
"expected_outputs": {
"Qs_kW": 5.03,
"Ql_kW": 10,
"Qt_kW": 15.03,
"SHR": 0.33466467
},
"working": "ΔT=30−20=10 K. ΔW=0.018−0.010=0.008 kg/kg. Qs=1.006×0.5×10=5.03 kW. Ql=0.5×2500×0.008=10.00 kW. Qt=5.03+10.00=15.03 kW. SHR=5.03/15.03=0.33466467."