HVAC Sensible/Latent Load Calculator

The current ledger marks this instrument verified clean within the source-bound verification corpus.

Status: VERIFIED_CLEANLifecycle: verified-clean

Inspectable records

Ledger state

The current ledger marks this instrument verified clean within the source-bound verification corpus.

Area
Thermodynamics, Fluids & Aero
Tranche
tranche-4
Evidence ID
t4-084
Ledger rows
1

No ledger note is attached.

Review findings

The underlying load formulas are standard under their stated assumptions, but the specification is incomplete and ambiguous about humidity-ratio units, dry-air basis, hfg, delta sign convention, total-load and SHR formulas, and zero-total-load handling. The honest label should explicitly state that the 0.68 latent constant requires grains/lb rather than a generic ΔW unit.

Formula and scope findings

  • The metric sensible formula Qs=1.006·ṁ·ΔT is correct for dry-air mass flow in kg/s, temperature difference in K or °C, and output in kW, but the required dry-air basis and sign convention are not stated.
  • The metric latent formula Ql=ṁ·hfg·ΔW is correct when hfg is in kJ/kg and ΔW is kg water/kg dry air, producing kW; however, hfg is not specified and varies with temperature.
  • The imperial sensible approximation 1.08·CFM·ΔT is valid for standard HVAC assumptions with CFM, temperature difference in °F, and output in BTU/h.
  • The imperial latent approximation 0.68·CFM·ΔW is valid when ΔW is in grains of water per pound of dry air, not when ΔW is expressed as lb/lb or kg/kg; the spec does not state this required unit.
  • The formulas for total load and sensible heat ratio are omitted. They should be Qt=Qs+Ql and SHR=Qs/Qt.
  • The entering-versus-leaving direction for ΔT and ΔW is unspecified. For positive cooling loads, the usual definitions are ΔT=Tin−Tout and ΔW=Win−Wout.

Unit assumptions

  • Metric calculations use ṁ in kg/s of dry air, ΔT in K or °C, ΔW in kg water/kg dry air, hfg in kJ/kg, and outputs in kW.
  • Imperial sensible calculations use CFM, ΔT in °F, and output in BTU/h.
  • Imperial latent calculations use ΔW in grains of water per pound of dry air; 1 lb/lb equals 7000 grains/lb.
  • The 1.08 and 0.68 constants assume approximately standard sea-level HVAC air conditions; they are not universal across altitude, pressure, or substantially different air density.
  • The worked cooling-load examples define ΔT=entering temperature−leaving temperature and ΔW=entering humidity ratio−leaving humidity ratio.

Boundary hardening

BREAK_CLAIMED · SELF_FLAGGED

The calculator has an unavoidable undefined-result trap when total load is zero: SHR becomes 0/0 or a nonzero value divided by zero. The specification also leaves the CFM-versus-mass-flow branch selection, humidity-ratio units, and load sign convention insufficiently defined, allowing materially different outputs or sign reversals.

Errata and corrections

No applied erratum is attached to this unique-name record.

Inspectable example

4 review vectors are recorded. One source-bound sample is shown below.

{
  "inputs": {
    "system": "metric",
    "mass_flow_kg_per_s": 0.5,
    "entering_temperature_C": 30,
    "leaving_temperature_C": 20,
    "entering_humidity_ratio_kg_per_kg_dry_air": 0.018,
    "leaving_humidity_ratio_kg_per_kg_dry_air": 0.01,
    "hfg_kJ_per_kg": 2500
  },
  "expected_outputs": {
    "Qs_kW": 5.03,
    "Ql_kW": 10,
    "Qt_kW": 15.03,
    "SHR": 0.33466467
  },
  "working": "ΔT=30−20=10 K. ΔW=0.018−0.010=0.008 kg/kg. Qs=1.006×0.5×10=5.03 kW. Ql=0.5×2500×0.008=10.00 kW. Qt=5.03+10.00=15.03 kW. SHR=5.03/15.03=0.33466467."
}