Inrush Current / Fuse & Breaker Sizing Estimator mechanism

The inspectable method record for Inrush Current / Fuse & Breaker Sizing Estimator, kept separate from implementation and qualification.

Status: VERIFIED_CLEANLifecycle: verified-clean

Model scope

The exact ambiguity requiring review is the undefined meaning and application of safety margin, plus the undefined relationship between estimated inrush and the recommended protection-device rating. The four outputs therefore use a clearly stated provisional interpretation for arithmetic verification only. The honest-label warning is necessary but insufficient to make this a code-compliant fuse or breaker selector; final selection must use the applicable electrical code, equipment documentation, conductor ratings, and protective-device time-current data.

  • The specification does not define how the safety margin is applied. The test vectors provisionally interpret safety_margin as a multiplicative factor, so 1.10 means 10% extra; it could instead mean a percentage such as 10.
  • The stated 1.25 × continuous-current rule is not a complete or universally applicable fuse/breaker-sizing method. Fuse and breaker selection depends on applicable code articles, conductor ampacity, equipment ratings, interrupting rating, coordination, ambient temperature, and time-current behavior.
  • The inrush multiplier table is only a rough heuristic. Motor inrush varies with motor design and starting method; transformer inrush varies with energization phase angle, residual flux, transformer design, source impedance, and duration.
  • The algorithm does not define how the estimated inrush current affects the recommended device rating. As provisionally interpreted, the output rating uses only 1.25 × continuous current × safety margin, while inrush is reported separately and does not influence device selection.
  • No rule is given for rounding the calculated value to an available standard fuse or breaker rating.
  • The input load type lists resistive, but the data needs specifically lists incandescent. Generic resistive loads do not necessarily have a 10× inrush multiplier; the supported load categories must be defined.

Units and conventions

  • All current values are interpreted as RMS amperes unless explicitly labeled otherwise.
  • In the fourth vector, 500 mA is converted to 0.500 A before calculation; mixing amperes and milliamperes without an explicit unit field is unsafe.
  • The provisional rating formula is recommended_rating_A = 1.25 × steady_current_A × safety_margin_factor.
  • The provisional inrush formula is inrush_current_A = steady_current_A × table_multiplier.
  • A safety_margin_factor of 1.00 means no additional margin; 1.10 means 10% additional margin, not 10 percentage points.
  • The 1.25 factor is treated as the specified NEC-style rule of thumb, not as a universal code-compliant device-selection rule.

Inspectable vector

One of 4 source-bound review vectors:

{
  "inputs": {
    "steady_current": 10,
    "steady_current_unit": "A",
    "load_type": "motor",
    "safety_margin": 1
  },
  "expected_outputs": {
    "recommended_rating_A": 12.5,
    "inrush_current_estimate_A": 60
  },
  "reference_data": {
    "continuous_current_factor": 1.25,
    "continuous_current_factor_source_convention": "NEC-style rule of thumb; widely tabulated 125% sizing heuristic, not a universal NEC device-rating table entry",
    "inrush_multiplier": 6,
    "inrush_multiplier_source_convention": "widely tabulated standard engineering rule-of-thumb value for a typical across-the-line induction motor"
  },
  "working": "1. Continuous-current basis = 1.25 × 10.0 A = 12.5 A.\n2. Apply safety margin = 12.5 A × 1.00 = 12.5 A.\n3. Estimated inrush = 6.0 × 10.0 A = 60.0 A.\n4. Provisional outputs: recommended rating = 12.5 A; inrush estimate = 60.0 A."
}

Failure boundary

BREAK_CLAIMED · SELF_FLAGGED

The estimator has hazardous boundary behavior unless it validates inputs: zero current produces a meaningless zero rating, negative current can produce invalid negative ratings under a literal signed interpretation, and a very large transformer current causes the inrush calculation to overflow to infinity. The transformer multiplier is also only specified as a 10–15x range, so the selected table endpoint must be documented.