Reinforced Concrete Beam — Singly Reinforced Flexural Capacity
The current ledger marks this instrument verified with errata that must be applied at binding time.
Inspectable records
Ledger state
The current ledger marks this instrument verified with errata that must be applied at binding time.
- Area
- Mechanical, Civil & Structural Engineering — Statics/Dynamics, Strength of Materials, Machine Design, Civil, HVAC, Vibration
- Tranche
- tranche-5
- Evidence ID
- t5-122
- Ledger rows
- 1
No ledger note is attached.
Review findings
The nominal-strength equations are standard under the stated Whitney-block assumptions, but the instrument cannot honestly claim complete ACI 318 design capacity or reinforcement checks without an ACI edition, rho-min/rho-max definitions, and a tension-controlled strain verification. The exact unresolved ambiguity is whether φ=0.9 is to be applied unconditionally or only after calculating the tensile strain and confirming the applicable ACI tension-controlled limit.
Formula and scope findings
- The formulas for steel ratio ρ, ρmin, and ρmax are not provided even though the instrument claims to check them.
- φ=0.9 is valid only when the tensile strain satisfies the applicable ACI 318 tension-controlled limit; the spec does not calculate c, εt, or otherwise verify that condition.
- The formula uses the Whitney equivalent rectangular compression block and is valid only for a singly reinforced rectangular section with a valid positive compression-block depth a less than d.
- ACI 318 edition is unspecified; strength-reduction factors and tension-controlled criteria can vary by edition and design provision.
- No explicit input constraints are specified for positive b and d, nonnegative As, fy, and f'c, or for preventing an over-reinforced/non-tension-controlled section from being labeled with φ=0.9.
Unit assumptions
- Inputs must use one coherent unit system: As and b·d in the same area units, fy and f'c in the same stress units, and d and a in the same length units.
- With As in mm², dimensions in mm, and stresses in MPa (N/mm²), a is in mm and Mn is in N·mm; reported kN·m equals Mn divided by 1,000,000.
- With As in in², dimensions in inches, and stresses in ksi, a is in inches and Mn is in kip·in; reported kip·ft equals kip·in divided by 12.
- The coefficient 0.85 is treated as the ACI equivalent rectangular concrete compression-block factor.
- The value φ=0.9 is assumed only after verifying the applicable ACI tension-controlled strain requirement; that verification is not possible from the supplied inputs alone.
Boundary hardening
Recorded hazards
- Division by zero occurs if b is zero; d is also required to be positive for a meaningful section and steel ratio.
- Negative or inconsistent units can produce meaningless capacities; automatic unit validation is required.
- If a is greater than or equal to d, the simplified expression can produce zero or negative nominal moment and must not be presented as a valid tension-controlled design capacity.
- Applying φ=0.9 without checking tensile strain can overstate design capacity for over-reinforced sections.
- ρmin and ρmax cannot be checked because their formulas, ACI edition, and any required code parameters are absent.
- The zero-steel case computes arithmetically but is not a reinforced-concrete flexural design and would generally fail minimum-reinforcement requirements once those requirements are defined.
Errata and corrections
Stress-test correction
{
"vector_inputs": {
"As": 300,
"fy": 500,
"fc": 40,
"b": 250,
"d": 450
},
"wrong_outputs": {
"a_mm": 14.823529,
"Mn_kN_m": 66.388235,
"phiMn_kN_m": 59.749412
},
"corrected_outputs": {
"a_mm": 17.647059,
"Mn_kN_m": 66.176471,
"phiMn_kN_m": 59.558824
},
"method": "a = As*fy/(0.85*fc*b) = 150000/8500 = 17.647059 mm, not 14.823529 (a ~1000/8500 arithmetic slip). Mn and phiMn recomputed downstream from the corrected a. rho/rho_min/rho_max/check flags do not depend on a and were unaffected."
}Inspectable example
4 review vectors are recorded. One source-bound sample is shown below.
{
"inputs": {
"As": 300,
"fy": 420,
"fc_prime": 28,
"b": 300,
"d": 500,
"units": "As mm²; fy and fc_prime MPa; b and d mm"
},
"expected_outputs": {
"a_mm": 17.6470588,
"Mn_kN_m": 61.8882353,
"phiMn_kN_m": 55.6994118,
"rho": 0.002,
"rho_min_check": "UNDETERMINED: rho_min formula/value not supplied",
"rho_max_check": "UNDETERMINED: rho_max formula/value not supplied"
},
"working": "Asfy = 300 × 420 = 126000 N.\\n0.85fc'b = 0.85 × 28 × 300 = 7140 N/mm.\\na = 126000 ÷ 7140 = 17.6470588 mm.\\nMn = 126000 × (500 − 17.6470588 ÷ 2) = 126000 × 491.1764706 = 61888235.3 N·mm = 61.8882353 kN·m.\\nφMn = 0.9 × 61.8882353 = 55.6994118 kN·m.\\nρ = As/(bd) = 300/(300 × 500) = 300/150000 = 0.002."
}Related workflows
No source-defined multi-instrument workflow membership is recorded.
Sources and evidence
These pointers bind the page to evidence. They do not grant authority or collapse verification into deployment.
VERIFIED_LEDGER.json · VERIFIED_WITH_ERRATAevidence-tranche5/tranche5-results.jsonSTRESS_TEST_CORRECTIONS_APPLIED.json