Transformer Turns Ratio & Sizing Calculator implementation
A source-bound implementation contract for Transformer Turns Ratio & Sizing Calculator; deployment and executable qualification remain separate.
Binding contract
This record describes what an executable surface must bind and validate. It does not claim that a public calculator, package, or production route is deployed.
- Record owner
- Guth Instruments
- Lifecycle
- verified-clean
- Evidence ID
- t4-054
- Effect
- Computation or source lookup only
Input and validation requirements
The zero-turn secondary input produces an undefined ratio and must be rejected. Signed-voltage inputs also expose an unresolved polarity/sign convention: signed and magnitude interpretations produce different ratio and current signs.
Required corrections
No binding erratum is attached to this unique-name record. Implementers must still preserve the declared units, domain, and failure behavior.
Inspectable interface fixture
The sample below is evidence for interface and validation tests, not a production implementation.
{
"inputs": {
"V1_V": 120,
"V2_V": 12,
"load_current_A": 5
},
"expected_outputs": {
"ratio_a": 10,
"secondary_voltage_V": 12,
"secondary_current_A": 5,
"primary_current_A": 0.5,
"required_VA": 60
},
"working": "a=V1/V2=120/12=10. I1=I2/a=5/10=0.5 A. VA=V2·I2=12·5=60 VA."