Transformer Turns Ratio & Sizing Calculator
The current ledger marks this instrument verified clean within the source-bound verification corpus.
Inspectable records
Ledger state
The current ledger marks this instrument verified clean within the source-bound verification corpus.
- Area
- Electrical & Electronics Engineering — Circuits, Power Systems, Electronics Lab
- Tranche
- tranche-4
- Evidence ID
- t4-054
- Ledger rows
- 1
No ledger note is attached.
Review findings
The core ideal-transformer relationships are standard, but the instrument fails its stated feature set because % regulation has no defined formula and required VA sizing is conflated with load apparent power. The honest-label text appropriately discloses ignored losses, but the UI must explicitly identify all results as ideal-model values and must not imply a certified or thermally sufficient transformer rating.
Formula and scope findings
- The turns-ratio identity a=N1/N2=V1/V2=I2/I1 is correct only for an ideal transformer with RMS AC quantities, negligible losses, and consistent primary/secondary labeling.
- No formula is provided for the claimed % regulation estimate. In the stated ideal model, regulation would conventionally be 0%, but that assumption and the regulation definition are not specified; a real-transformer regulation estimate requires additional parameters.
- VA=V·I correctly computes apparent power, but it does not by itself determine a required transformer VA rating. A sizing rating normally requires a design margin, duty cycle, temperature/thermal constraints, and possibly inrush considerations.
- The input alternatives are underspecified: the spec does not state how to derive missing V2 from N1,N2 and V1, or missing current from a supplied VA, nor how conflicting simultaneous inputs are handled.
Unit assumptions
- V1 and V2 are RMS AC voltages in volts, measured on consistently labeled primary and secondary windings.
- I1 and I2 are RMS currents in amperes; N1 and N2 are winding turns and therefore dimensionless counts.
- The transformer operates at the same frequency on both windings and is modeled as ideal, so V1/V2=N1/N2 and I2/I1=N1/N2.
- VA is apparent power in volt-amperes, calculated using RMS voltage multiplied by RMS current, with power factor excluded.
- A supplied load current is treated as secondary load current I2; a supplied VA value is treated as secondary apparent load power unless explicitly stated otherwise.
- A current ratio or voltage ratio must not use a zero denominator, and all voltage, current, and turns inputs must be positive for normal transformer operation.
Boundary hardening
BREAK_CLAIMED · SELF_FLAGGED
The zero-turn secondary input produces an undefined ratio and must be rejected. Signed-voltage inputs also expose an unresolved polarity/sign convention: signed and magnitude interpretations produce different ratio and current signs.
Errata and corrections
No applied erratum is attached to this unique-name record.
Inspectable example
4 review vectors are recorded. One source-bound sample is shown below.
{
"inputs": {
"V1_V": 120,
"V2_V": 12,
"load_current_A": 5
},
"expected_outputs": {
"ratio_a": 10,
"secondary_voltage_V": 12,
"secondary_current_A": 5,
"primary_current_A": 0.5,
"required_VA": 60
},
"working": "a=V1/V2=120/12=10. I1=I2/a=5/10=0.5 A. VA=V2·I2=12·5=60 VA."