Wire Gauge (AWG/SWG) ↔ Diameter/Area Converter
The current ledger marks this instrument verified clean within the source-bound verification corpus.
Inspectable records
Ledger state
The current ledger marks this instrument verified clean within the source-bound verification corpus.
- Area
- Electrical & Electronics Engineering — Circuits, Power Systems, Electronics Lab
- Tranche
- tranche-7
- Evidence ID
- t7-060
- Ledger rows
- 1
No ledger note is attached.
Review findings
The AWG diameter equation is valid, and the area and resistance arithmetic above is consistent with the stated assumptions. Verdict is NEEDS_REVIEW because SWG data/algorithm, diameter-standard selection, conductor material, resistivity convention, temperature, valid ranges, and rounding behavior are not specified. The honest label should say that resistance is nominal conductor resistance at a stated temperature and material, not guaranteed installed-cable resistance.
Formula and scope findings
- The AWG diameter formula is correct for nominal American Wire Gauge: d(mm)=0.127×92^((36−AWG)/39).
- Cross-sectional area is not stated but must be computed as A=πd²/4.
- Resistance requires R=ρL/A, with diameter converted from mm to m before calculating SI resistance.
- No SWG conversion algorithm or SWG table is supplied, although SWG is an advertised input/output standard. AWG and SWG numbers are not interchangeable.
- Diameter-to-gauge conversion is underspecified: the instrument must identify whether the diameter is being interpreted as AWG or SWG, and should define rounding and valid gauge ranges.
- Resistance cannot be determined from gauge alone without conductor material, resistivity convention, and temperature. If the instrument claims copper resistance, that must be stated explicitly.
Unit assumptions
- AWG diameters are nominal bare-conductor diameters in millimetres, using the standard 0.127 mm AWG-36 reference diameter.
- Area is reported in mm².
- Resistivity values are assumed to be at 20 °C; resistance uses R=ρL/A.
- For resistance calculations, area in mm² is converted to m² by multiplying by 10^-6.
- Ω/km uses L=1000 m; Ω/1000 ft uses the exact conversion 1000 ft=304.8 m.
- The test vectors explicitly assume annealed copper with ρ=1.68×10^-8 Ω·m, a widely tabulated standard value at 20 °C.
Boundary hardening
BREAK_CLAIMED · SELF_FLAGGED
The specification does not define rejection behavior for zero diameter, does not identify the exact valid AWG range, and does not require an explicit AWG-versus-SWG selector or diameter unit. These omissions permit undefined outputs and materially different numeric results.
Errata and corrections
No applied erratum is attached to this unique-name record.
Inspectable example
4 review vectors are recorded. One source-bound sample is shown below.
{
"inputs": {
"standard": "AWG",
"gauge": 36,
"material": "annealed copper",
"temperature_C": 20,
"requested_resistance_lengths": [
"1 km",
"1000 ft"
]
},
"expected_outputs": {
"diameter_mm": 0.127,
"area_mm2": 0.012667687,
"resistance_ohm_per_km": 1326.21,
"resistance_ohm_per_1000ft": 404.23
},
"reference_data": {
"awg_row": {
"gauge": 36,
"diameter_mm": 0.127,
"source_convention": "AWG standard, widely tabulated standard value"
},
"copper_resistivity_ohm_m_20C": 1.68e-8,
"source_convention_resistivity": "widely tabulated standard value for copper at 20 °C",
"pi": 3.141592653589793,
"source_convention_pi": "mathematical constant",
"metres_per_1000ft": 304.8,
"source_convention_length": "exact SI/international-foot conversion"
},
"working": "d=0.127 mm (the exact AWG-36 table entry). A=πd²/4=3.141592653589793×(0.127²)/4=3.141592653589793×0.016129/4=0.012667687 mm². Convert area: A=0.012667687×10^-6=1.2667687×10^-8 m². R/km=ρL/A=(1.68×10^-8 Ω·m×1000 m)/(1.2667687×10^-8 m²)=1326.21 Ω/km. R/1000 ft=(1.68×10^-8×304.8)/(1.2667687×10^-8)=404.23 Ω/1000 ft."
}Related workflows