NTU-Effectiveness Heat Exchanger Calculator

The current ledger marks this instrument verified with errata that must be applied at binding time.

Status: VERIFIED_WITH_ERRATALifecycle: verified-with-binding-errata

Inspectable records

Ledger state

The current ledger marks this instrument verified with errata that must be applied at binding time.

Area
Thermodynamics, Fluids & Aero
Tranche
tranche-4
Evidence ID
t4-180
Ledger rows
1

No ledger note is attached.

Review findings

The NTU and capacity-ratio definitions and the supplied counterflow correlation are standard under the stated assumptions. The specification needs explicit inlet-temperature inputs, outlet equations, a complete configuration-to-correlation mapping, the Cr=1 limit, unit validation, and positive-capacity constraints before it can be labeled as a complete calculator.

Formula and scope findings

  • NTU=UA/Cmin is standard when U is an overall heat-transfer coefficient in W/(m²·K), A is in m², and Cmin is in W/K.
  • Cr=Cmin/Cmax is standard, but Cmin and Cmax must be computed as m_dot·cp using consistent units.
  • The counterflow effectiveness formula is correct for Cr≠1: ε=(1−exp(−NTU·(1−Cr)))/(1−Cr·exp(−NTU·(1−Cr))).
  • For counterflow Cr=1, the displayed formula becomes 0/0 and must be replaced by its limiting form ε=NTU/(1+NTU).
  • Configuration-specific correlations are not provided for parallel flow, crossflow, multipass, or other configurations; the calculator cannot safely accept a generic configuration without those formulas.
  • Outlet temperatures require inlet hot and cold temperatures, which are absent from the declared inputs.

Unit assumptions

  • U is in W/(m²·K).
  • A is in m².
  • Mass flow rates are in kg/s.
  • Specific heat capacities are in J/(kg·K), so each capacity rate C=m_dot·cp is in W/K.
  • Temperatures used in temperature differences may be in °C or K; absolute temperatures are not needed for these formulas, but both inlet temperatures must use the same scale.
  • q is reported in W and outlet temperatures in °C in the test vectors.

Boundary hardening

BREAK_CLAIMED · SELF_FLAGGED

The raw counterflow formula is undefined at Cr=1 because it becomes 0/0, requiring the limiting expression epsilon=NTU/(1+NTU). A zero capacity rate makes NTU divide by zero and should be rejected. These are concrete failure points unless explicit boundary and input validation branches are implemented.

Errata and corrections

Tranche errata

q_W / T_hot_out / T_cold_out · vector 1

q 132,891.81, Tho 116.42, Tco 59.74

q 265,783.63, Tho 52.83, Tco 99.48

q exactly halved; her epsilon 0.7948 is correct and outlets inherit the halving

Inspectable example

4 review vectors are recorded. One source-bound sample is shown below.

{
  "inputs": {
    "configuration": "counterflow",
    "U_W_m2K": 500,
    "A_m2": 10,
    "m_hot_kg_s": 0.5,
    "cp_hot_J_kgK": 4180,
    "m_cold_kg_s": 0.8,
    "cp_cold_J_kgK": 4180,
    "T_hot_in_C": 180,
    "T_cold_in_C": 20
  },
  "expected_outputs": {
    "epsilon": 0.7948075,
    "q_W": 132891.81,
    "T_hot_out_C": 116.4154,
    "T_cold_out_C": 59.7404
  },
  "working": "Ch=0.5·4180=2090 W/K; Cc=0.8·4180=3344 W/K; Cmin=2090; Cmax=3344; Cr=2090/3344=0.625. UA=500·10=5000 W/K. NTU=5000/2090=2.3923445. x=NTU·(1−Cr)=2.3923445·0.375=0.8971292. exp(−x)=exp(−0.8971292)=0.4077385. ε=(1−0.4077385)/(1−0.625·0.4077385)=0.5922615/0.7451634=0.7948075. ΔTin=180−20=160 K. q=0.7948075·2090·160=132891.81 W. Th,out=180−132891.81/2090=180−63.5846=116.4154 °C. Tc,out=20+132891.81/3344=20+39.7404=59.7404 °C."
}