Transformer Efficiency & Losses Estimator
The current ledger marks this instrument verified clean within the source-bound verification corpus.
Inspectable records
Ledger state
The current ledger marks this instrument verified clean within the source-bound verification corpus.
- Area
- Electrical & Electronics Engineering — Circuits, Power Systems, Electronics Lab
- Tranche
- tranche-4
- Evidence ID
- t4-066
- Ledger rows
- 1
No ledger note is attached.
Review findings
The honest label is appropriate, but the implementation needs an explicit full-load copper-loss reference, decimal-versus-percent load convention, output-power formula, valid input constraints, and a defined efficiency-curve sweep before the specification can pass.
Formula and scope findings
- η=Pout/(Pout+Pcu+Pfe) is standard when Pout is real output power and Pcu and Pfe are real losses in watts.
- Pcu∝(load%)² is incomplete as an executable formula: it must define a reference copper loss, normally Pcu(load)=Pcu_full_load×load_fraction².
- The specification does not state whether the copper-loss input is the full-load copper loss; this is required to calculate load-dependent copper loss.
- The specification uses load% while the input is called load fraction; the representation must be explicitly defined as either a decimal fraction from 0 to 1 or a percentage from 0 to 100.
- No explicit formula is provided for output power. Under the usual transformer model, Pout=rated_VA×load_fraction×PF.
- An efficiency curve requires a defined load sweep, domain, step size, and treatment of invalid load fractions; these are missing.
Unit assumptions
- rated_VA is apparent power in VA.
- copper_loss_full_load_W and core_loss_W are real power losses in watts.
- PF is dimensionless and lies from 0 to 1; it is assumed constant over the load curve.
- load_fraction is a decimal fraction from 0 to 1, so 25% is entered as 0.25.
- Pout=rated_VA×load_fraction×PF, producing watts because VA×PF is treated as real watts.
- Core loss Pfe is assumed constant with load and frequency, voltage, and waveform.
Boundary hardening
BREAK_CLAIMED · SELF_FLAGGED
The zero-output, zero-loss combination produces an undefined 0/0 efficiency, and the specification does not define behavior for load fractions above 1.0 or the PF unit convention.
Errata and corrections
No applied erratum is attached to this unique-name record.
Inspectable example
4 review vectors are recorded. One source-bound sample is shown below.
{
"inputs": {
"rated_VA": 1000,
"copper_loss_full_load_W": 40,
"core_loss_W": 10,
"PF": 0.8,
"load_fraction": 0.5
},
"expected_outputs": {
"Pout_W": 400,
"Pcu_W": 10,
"Pfe_W": 10,
"total_loss_W": 20,
"efficiency": 0.9523809523809523,
"efficiency_percent": 95.23809523809523
},
"working": "Pout=1000×0.5×0.8=400 W. Pcu=40×0.5²=40×0.25=10 W. Pfe=10 W. Total loss=10+10=20 W. η=400/(400+10+10)=400/420=20/21=0.9523809523809523=95.23809523809523%."
}Related workflows
No source-defined multi-instrument workflow membership is recorded.
Sources and evidence
These pointers bind the page to evidence. They do not grant authority or collapse verification into deployment.
VERIFIED_LEDGER.json · VERIFIED_CLEANevidence-tranche4/tranche4-results.jsonBOUNDARY_HAZARD_CATALOG.json